Product Specification

Power rating 40kVA / 36kW
Topology Double-conversion online UPS
Operation Frequency 50/60 Hz (40 to 72 Hz)
Power input factor > 0.99 typical
Current input distortion ≤5% THD
Nominal input voltage 400 / 230V, 4 wires (380 / 415V selectable)
Input voltage level -15%, + 20% of the figure (400V) at 100% load without draining the battery
Nominal output voltage 400/230, 4 wires (380 / 415V selectable)
Variation in output voltage (± 1% Static; <5% Dynamic at 100% resistive free change, <20 ms response time
Battery 432V (216 Cells * 6 strings (max), With default internal battery)
Charging method ABM Cyclic Charging
Efficiency Mode> 98% High-efficiency Mode> 94% Double-conversion
Overload 150% for 1 minute, 125% for 10 minutes,> 150% for 150ms
UPS bypass Automatically if the UPS is overloaded or malfunctions
Parallel technology Hot Sync® Technology
Dimension Width x Diamter x Height (mm) 600 x 800 x 1876
Cabinet rating IP20 with washable dust filter
Display Graphic LCD with blue backlight
LEDs 4x LEDs for notifications and alarms
Alarm sound Yes
Operating temperature 0ºC to + 40ºC The maximum recommended battery temperature. + 25ºC
Storage temperature -25ºC to + 55ºC With batteries + 15ºC to + 25ºC Without batteries
Humidity level 5–95%, Non-condensing